Question posted - December 24 to January 6, 2013:

How can it be determined if moisture within a CMU wall is causing repeated coating failure? If so, can the source of moisture entry be accurately identified for correction?



More items for Building Envelope


Selected Answers

From Tim Davis of Glidden Professional on January 2, 2013:
     I would agree with Channing on the need for additional information, prior to drawing a conclusion. In addition to his points, the investigation should also look at the interior operations of the building. Is there is a source of humidity that could be drawn into the CMU walls such as heaters, operations within the building, etc. If so,  then there may be a vapor drive occurring. Even if the walls are sealed, the vapor could be condensing at or above the roof deck and be carried back to the walls. The moral of the story would be that if the moisture source is not obvious, then the investigation becomes very complex. A dew point anaylsis of the facility may indicate that water vapor is condensing within the wall cavity and causing the issue. Combining a dew-point analysis with an air infiltration/exfiltration survey may prove beneficial to the investigation. It may be surprising to some, to find that the insulation and air sealing techniques can contribute to moisture issues

From Channing Lewis of ROMA - Eco Sustainable Building Technologies on January 1, 2013:
     For starters, it would help to provide more information about this particular CMU wall...is it freestanding and above grade, or is it backfilled on the exterior side or open to the air? Also, is the repeated failure in the same area or widespread across the entire surface? Look for discoloration (typically lighter in color, sometimes chalky).
      If the CMU wall is older than 5 years, have the joints shown any sign of cracking or any signs of organic growth? This is a sure sign of water intrusion. Is the failure isolated to the bottom or top of the vertical wall? "Bubbling" of elastomeric coatings is often due to moisture intrusion as well. If this is a covered structure, and CMU is contiguous to the roof, you may want to start at the top and work down performing a leak test. There are multiple tpes of CMU "block filler/primers" that will help, but if there is not a moisture/vapor barrier on the exterior side, they will ultimate fail and the water will eventually find daylight at the weakest point of exit, following gravity.

Please sign in to submit your answer this question

   

Tagged categories: Coating failure; Concrete masonry units (CMU); Humidity and moisture


Current PSF Question | Submit a PSF Question | Full PSF Archive

Graco Inc.
Eco-Friendly Surface Prep

• Blast with 92% less dust
• Use less media
• Less containment & disposal costs
Graco® EcoQuip® Vapor Abrasive® Blast Equipment Learn more


Pratt & Lambert Paints
THE PREMIUM STANDARD FOR PROFESSIONAL PAINTERS

Pro-Hide® Gold Ultra is the ideal paint for your customers and your business. It delivers a beautiful finish, outstanding hide, easy application and excellent touch-up. And now pros can bid on even more jobs, because Pro-Hide Gold Ultra is MPI® Approved for interior gloss levels 1-5.


Keim Mineral Coatings
Color/Protection for Concrete that Won’t Peel

Concretal® Stains & Finishes penetrate, forming permanent chemical bonds within that can never peel. And mineral pigments don't fade-no matter how harsh the exposure.


PPG Pittsburgh Paints
Wonder-Pro

This high-production, quality "workhorse" professional latex paint is formulated to meet
the requirements of the professional painter and building contractors/managers. It is easy to apply by brush, roller or spray, is high-hiding and has spatter-free application, drying quickly for fast touch-up and recoat.


KTA-Tator, Inc. - Corporate Office
KTA Laboratory Services

Fully equipped lab to solve
the most challenging
coatings problems.
Contact: Cindy O'Malley, 412-788-1300 x180


Atlas Material Testing Technology

Helping You Put Your Products To The Test

• Outdoor Accelerated
Weathering
• Laboratory Testing
Services
• Accelerated Weathering
Instruments

www.atlas-mts.com atlas.info@ametek.com

 
 
 

Technology Publishing Co., 2100 Wharton Street, Suite 310, Pittsburgh PA 15203-1951

TEL 1-412-431-8300  • FAX  1-412-431-5428  •  EMAIL webmaster@durabilityanddesign.com


The Technology Publishing Network

Durability + Design PaintSquare the Journal of Protective Coatings & Linings Paint BidTracker

 

© Copyright 2012-2016, Technology Publishing Co., All rights reserved